Product Information

Overview

Introducing the MX32 measurement and alarm unit suitable for the protection of equipment and personnel in atmospheres, which may contain flammable and toxic gases. Available with one or two channels, the MX 32 offers tailor-made detection capabilities and exceptional programming possibilities compatible with a wide range of fixed gas detectors.

The total cost of ownership is enhanced by easy installation and operating flexibility.

Specification

Manufacturer:

OLDHAM SA

Function:

Gas monitor

Presentations:

Wall-mounted box, Noryl type

Capacities:

1 or 2 channels

Measurement:

Continuous

Display:

Liquid crystal, fixed or scrolling

Alarms:

2 independent alarm thresholds per channel
Individual programming, by increasing or decreasing
Manual or automatic acknowledgement

Visual Alarms:

2 red LED + gas alarms per channel
1 yellow LED fault per channel

Audio Alarms:

Buzzer

Relays:

2 gas alarm relays per channel
One common relay for faults
Type of contact : NO or NC, programmable by jumpers

Power supply:

115 Vac or 230 Vac
24 Vdc

Power consumption:

30 W

Relay max. resistive

 

Breaking Capacity:

2A/230 V AC / 30 V DC

Weather protection:

IP 66

Detector connections per channel

Bridge type:

1 detector : maximum distance 300 m (3 x 1,5 mm2)
2 detectors : utilization of a junction box (Please consult us)

Detector with transmitter:

One to five 2-wire detectors, 4-20 mA
One 3-wire detector, 4-20 mA
Cable 3 x 1.5 mm2 (32 Ω max. in loop mode)

Fire detectors:

One to five detectors : cable 2 x 0.65 mm2

Flame detectors:

One 3-wire detector

 

Cable 3 x 1.5 mm2 (4,8 Ω max. in loop mode)

Miscellaneous

Weight:

1,750 g

Acknowledgement:

Manual or automatic

Operating temperature :

-20°C to +55°C

Relative humidity:

5% to 95% RH

Complies with EMC and low-voltage directives

 

Documentation
Oldham MX 32 Controller Literature Sheet (English)
Oldham MX 32 Controller Manual (English)
ATEX CATEGORY (1) (2)
  • Printer-friendly versionPrinter-friendly version

Product Types

  • Fixed Controllers
  • Fixed Transmitters
  • Fixed Accessories
  • Legacy Products
  • Product Policies

Share Your Success

See our full line of fixed gas detection products.

Share Your Success

Help us save more lives. Share your success with using Oldham fixed gas detection products and services.

You are here

Home

We’re here to help

Americas: +(1) 1-800-DETECTS
EMEA: +(33) 3 21 60 80 80
Asia-Pacific: +(86) 21 5899 3279

Feedback

Please take our Customer Satisfaction Survey.

The Industrial Scientific Family of Companies

Industrial Scientific: Portable Gas DetectorsOldham Gas: Fixed Gas DetectorsPredictive Solutions: Safety Software

Terms of Use | Privacy Statement

Copyright 2013 Oldham Gas. All Rights Reserved. Web site by Impactiv, Inc.